UPS COVER CORE ONE 3K
COVER Online Double-Conversion uninterruptible power supply, 3kVA/3kW. Plug@Play. Phase configuration 1:1. Rack/Tower cabinet (no batteries). Adjustable charger 1-8A
11-COR1-0030
CHARACTERISTICS
|
|
BACKUP TIME
| Internal batteries | Load | Backup time [min] |
| CORE ONE 3K | ||
| 6 x 9Ah | 100% | 4 |
| 75% | 6 | |
| 50% | 11 | |
| 25% | 28 |
| EBM CORE 3K | Load | Backup time [min] |
| CORE ONE 3K | ||
| UPS + 1xEBM (3 x 6 x 9Ah) | 100% | 20 |
| 75% | 28 | |
| 50% | 47 | |
| 25% | 129 | |
| UPS + 2xEBMs (5 x 6 x 9Ah) | 100% | 38 |
| 75% | 53 | |
| 50% | 90 | |
| 25% | 201 | |
| UPS + 3xEBMs (7 x 6 x 9Ah) | 100% | 56 |
| 75% | 79 | |
| 50% | 151 | |
| 25% | 321 |
TECHNICAL SPECIFICATIONS
| Model | CORE ONE 3K |
| Power | 3kVA / 3,0kW |
| Phases In/Out | 1:1 |
| Input | |
| Nominal voltage | 208 / 220 / 230 / 240 Vac |
| Voltage range | 100 ÷ 300 Vac |
| Nominal frequency | 50 / 60Hz |
| Frequency range | 40 ÷ 72 Hz |
| THDi | <3% |
| Input power factor | >0,99 |
| Output | |
| Nominal voltage | 208 / 220 / 230 / 240 Vac |
| Power factor | 1 |
| Voltge regulation static/dynamic | ±1% / ±3% |
| Nominal frequency | 50 / 60 ± 0,05 Hz |
| Overloads capability | 110% - bez limitu, 130% - 5min., 140% - 30s., >140% - 1,5s. |
| Efficiency in OnLine mode | >93% |
| Efficiency in ECO mode | >99% |
| Crest factor | 3:1 |
| Switching time | 0ms |
| Output sockets | 8 x IEC 320 C13 1 x IEC 320 C19 |
| Batteries | |
| Cold start | Yes |
| Internal batteries possibility | 6 x 9Ah/12V |
| Nominal voltage | 72Vdc |
| Charger curent | 1÷8A |
| Charging time | 3 – 8 hours up to 90% capacity (configurable) |
| Charging cycle | According to DIN 41773 with automatic charging shutdown according to current and voltage criteria, with time control. |
| Dimensions and weights | |
| Dimensions (S x G x W) | 438 x 630 x 88 (2U) |
| Weight | 27,5 kg |
| Signaling and communication ports | |
| Operating status indicator | LCD + audible alarm |
| Communication | RS232, USB, TVSS, EPO, slot SNMP |
| Environmental conditions | |
| Noise level | <48 dB |
| Operating temperature for UPS | 0°C ÷ 45°C |
| Recommended operating temperature | 15°C ÷ 25°C |
| Storage temperature | -25°C ÷ 55°C |
| Humidity | 0 ÷ 95% (non-condensing) |
| Cerifications | |
| Interference immunity | EN 62040-2: 2016, EMC CE |
| Safety | EN 62040-1: 2017, EN 62040-3: 2011, LVD, CE, UKCA |
| Environmental compatibility | EN IEC 63000: 2018, EN 62321, RoHS |
| Optional accesories | |
| - SNMP card | |
| - RS485 card (Modbus) | |
| - AS 400 mini (dry-contact) card | |
| - Environmental sensor (EMD) | |
| - Rail kits for Rack 19'' (Rail kit) | |
| - Remote Emergency Power Off button | |
| - External battery modules (EBM) | |
Due to constant product improvement all specifications are subject to change without notice.
- Apparent power [kVA]
- 3
- Active power [kW]
- 3
- Technology:
- VFI-SS-111 (OnLine DoubleConversion)
- Phase In/Out:
- 1:1
- Output PF:
- 1
- Max internal batteries
- 6
Related Products ( 16 other products in the same category )