UPS Cover NGS 40 kVA
COVER Online Double-Conversion uninterruptible power supply, 40kVA/40kW. Tower cabinet without batteries. Capable of installing up to 144 x 9Ah batteries. 3:3 phase configuration.
11-NGS0-0400
CHARACTERISTICS
|
|
TECHNICAL SPECIFICATIONS
Model | NGS 40K |
Power factor | 40kVA / 40kW |
Phases In/Out | 3:3 |
Design | Tower |
Input | |
Nominal voltage | 380 / 400 / 415 Vac |
Voltage range | -43% ÷ +20% |
Nominal frequency | 50 / 60Hz |
Frequency range | -20% ÷ +20% |
THDi | <3% |
Input power factor | ≥0,99 |
Output | |
Nominal voltage | 380 / 400 / 415 Vac |
Power factor | 1,0 |
Voltage regulation statis/dynamic | ±1% / ±2% |
Nominal frequency | 50 / 60 ± 0,05 Hz |
Overload caability | 110% - 60 min., 125% - 10 min., 150% - 60 s |
Short circuit capability | 340% of nominal curent by 200 ms |
Efficiency in OnLine mode | >96% |
Efficiency in ECO mode | 99% |
Crest factor | 3:1 |
Switching time | 0ms |
Batteries | |
Cold start | yes (opcja) |
Type of batteries | VRLA, AGM, gel |
Batteries range | 36 - 44 pcs x 12V |
Max quantity of internal batteries | 144pcs x 9Ah |
Max charging curent | 13A |
Charging type | 3 – 8 hours up to 90% capacity (configurable) |
Charging cycle | According to DIN 41773 with automatic charging shutdown according to current and voltage criteria, with time control. |
Dimensions and weights | |
Dimensions (S x G x W) | 500 x 840 x 1400mm |
Weight w/o batteries | 140,0 kg |
Weight with batteries | 528,8 kg |
Signaling and communication ports | |
Operating status indicator | LCD + LED + alarm dźwiękowy |
Communication | USB, RS232, RS485, Modbus, DryContact, REPO, slot SNMP |
Environmental conditions | |
Noise level | <58 dB @ load 100%, <52 dB @ load 50% |
Operating temperature for UPS | 0°C ÷ 40°C |
Recommended operating temperature | 15 °C ÷ 25 °C |
Storage temperature | -25°C ÷ 55°C |
Humidity | 0 ÷ 95% (non-condensing) |
Cerifications | |
Interference immunity | EN 62040-2:2005, EN 62040-2:2006 |
Safety | IEC62040-1-1, CE, 62040-3 :2001 |
Optional accesories | |
- SNMP card | |
- Battery temperature compensation kit | |
- Environmental sensor (EMD) | |
- Remote Emergency Power Off button | |
- External maintenance bypass | |
- Parallel cards | |
- Remote LCD panel | |
- Battery Cold start | |
- Backfeed protection |
Due to constant product improvement all specifications are subject to change without notice.
- Apparent power [kVA]
- 40
- Active power [kW]
- 40
- Technology:
- VFI-SS-111 (OnLine DoubleConversion)
- Phase In/Out:
- 3:3
- Output PF:
- 1
- Max internal batteries
- 144
Related Products ( 16 other products in the same category )